DP2000G Graphic Program Controller
DP2000G Graphic Program Controller
Graphic Program Controller/Setter DP-G Series
DP2000G series is a graphic program controller specially designed for wide range control. This control unit divides a control domain into a high region and a low region and controls extensively by changing two sensors for each region at a set point automatically.
Adjustment mode (1st output) |
Model No. |
ON-OFF pulse type |
DP2110G000-G10 |
ON-OFF servo type (standard load specification) |
DP2120G000-G10 |
Current output type |
DP2130G000-G10 |
SSR drive pulse type |
DP2150G000-G10 |
Voltage output type (general type) |
DP2160G000-G10 |
ON-OFF servo type (minute load specification) |
DP2180G000-G10 |
Current output type (high accuracy type) |
DP21A0G000-G10 |
Current output type (high accuracy type) |
DP21B0G000-G10 |
Voltage output type (high accuracy type) |
DP21C0G000-G10 |
คุณสมบัติ
คุณสมบัติ
- Easy-to-view color liquid crystal display provides great visibility into various data such as program patterns
- In addition to collective display, various monitoring screens are available including enlarged numeric display, bar graph display and trend display
- Easy-to-use setting menu in Japanese
- 28-point contact output, 16-point contact input, analog transmission output (option) and communication interface (option) are provided, allowing easy system construction
- Comes as standard with parameter editing software for PC
- The setter model provides a digital output type, allowing error-free program pattern signal output
ข้อมูลเฉพาะ
ข้อมูลเฉพาะ
Controller specification
- Input points: 2 points (Rang-R, Rang-H)
- Input signal: Thermocouple: B, R, S, K, E, J, T, etc.
- DC voltage: ±10 mV, ±20 mV, ±50 mV, ±100 mV, ±5 V, ±10 V
- DC current: 20 mA
- Resistance thermometer: Pt100, JPt100, etc.
- Accuracy rating: ±0.1%
of input span ±1 digit (under standard operating conditions) * There are separate detailed rating descriptions. - Reference junction compensation accuracy: K, E, J, T, N, Platinel II: ±0.5°C or lower
- Other than above: ±1.0°C or lower
- Sampling rate: Approx. 0.1 second
- Burnout: Burnout is provided as standard for thermocouple, DC voltage (±50 mV or less) and resistance thermometer.
- Rated power supply voltage: 100 V to 240 V AC 50/60 Hz (universal power supply)
- Weight: Approx. 1.7 kg
- Output format: Current output type, ON-OFF pulse type, Voltage output type, SSR drive pulse type
- Adjustment setting value: PID 8 types
- P: 0% to 999.9% (0 for 2 position operation)
- I: 0 to 9999 seconds (0 is equivalent to infinity)
- D: 0 to 9999 seconds
- ON-OFF pulse type: Output signal: ON-OFF pulse conductive signal
- Contact capacity: Resistive load 100 V to 240 V AC 30 V DC, 5 A or less Inductive load 100 V to 240 V AC 30 V DC, 2.5 A or less
- ON-OFF servo type:
- Output signal: ON-OFF servo conductive signal
- Contact capacity: Standard load specification:
- Resistive load 100 V to 240 V AC 30 V DC, 5 A or less
- Inductive load 100 V to 240 V AC 30 V DC, 2.5 A or less
- Minute load specification:
- Resistive load 100 V to 240 V AC 30 V DC, 20 mA or less
- Inductive load 100 V to 240 V AC 30 V DC, 20 mA or less
- Current output type: Output signal: 4 mA to 20 mA DC or 1 mA to 5 mA
- Load resistance: 750 Ω or less
- SSR drive pulse type: Output signal: ON-OFF pulse voltage signal
- Output voltage: ON voltage 12 V DC ±20%, OFF voltage 0.8 V DC or lower
- Output signal: Output signal 0 V to 10 V
- Output impedance: Approx. 10 Ω
- Number of alarm points: 4 points + 4 points (extended allocation setting)