DP10A0G000-G10
DP10A0G000-G10
Graphic Program Controller/Setter DP-G Series
DP1000G series is a graphic program controller employed high visibility 5.6 TFT color LCD display. Maximum 200 types of program pattern (Maximum 400 steps) are stored and performance pattern is selectable. Control cycle of 0.1 sec, 5 digits display, high speed, and high accuracy of ±0.1% indicating accuracy are realized.
Product Details |
|
Control mode (output No.1) |
Current output type (high accuracy type) |
Control mode (output No.2) |
None |
Communications interface |
|
Transmission signal output 1 |
|
Transmission signal output 2 |
|
Transmitter power supply |
|
Case color |
Gray |
External input/ output signal |
Digital input/ output (non-voltage contact input) |
Features
Features
- Easy-to-view color liquid crystal display provides great visibility into various data such as program patterns
- In addition to collective display, various monitoring screens are available including enlarged numeric display, bar graph display and trend display
- Easy-to-use setting menu in Japanese
- 28-point contact output, 16-point contact input, analog transmission output (option) and communication interface (option) are provided, allowing easy system construction
- Comes as standard with parameter editing software for PC
- The setter model provides a digital output type, allowing error-free program pattern signal output
Specifications
Specifications
Controller specification
- Input signal: Thermocouple: B, R, S, K, E, J, T, etc.
- DC voltage: ±10 mV, ±20 mV, ±50 mV, ±100 mV, ±5 V, ±10 V
- DC current: 20 mA
- Resistance thermometer: Pt100, JPt100, etc.
- Accuracy rating: ±0.1%
of input span ±1 digit (under standard operating conditions) * There are separate detailed rating descriptions. - Reference junction compensation accuracy: K, E, J, T, N, Platinel II: ±0.5°C or lower
- Other than above: ±1.0°C or lower
- Sampling rate: Approx. 0.1 second
- Burnout: Burnout is provided as standard for thermocouple, DC voltage (±50 mV or less) and resistance thermometer.
- Rated power supply voltage: 100 V to 240 V AC 50/60 Hz (universal power supply)
- Weight: Approx. 1.7 kg
- Output format: Current output type, ON-OFF pulse type, Voltage output type, SSR drive pulse type
- Adjustment setting value: PID 8 types
- P: 0% to 999.9% (0 for 2 position operation)
- I: 0 to 9999 seconds (0 is equivalent to infinity)
- D: 0 to 9999 seconds
- ON-OFF pulse type: Output signal: ON-OFF pulse conductive signal
- Contact capacity: Resistive load 100 V to 240 V AC 30 V DC, 5 A or less Inductive load 100 V to 240 V AC 30 V DC, 2.5 A or less
- ON-OFF servo type:
- Output signal: ON-OFF servo conductive signal
- Contact capacity: Standard load specification:
- Resistive load 100 V to 240 V AC 30 V DC, 5 A or less
- Inductive load 100 V to 240 V AC 30 V DC, 2.5 A or less
- Minute load specification:
- Resistive load 100 V to 240 V AC 30 V DC, 20 mA or less
- Inductive load 100 V to 240 V AC 30 V DC, 20 mA or less
- Current output type: Output signal: 4 mA to 20 mA DC or 1 mA to 5 mA
- Load resistance: 750 Ω or less
- SSR drive pulse type: Output signal: ON-OFF pulse voltage signal
- Output voltage: ON voltage 12 V DC ±20%, OFF voltage 0.8 V DC or lower
- Output signal: Output signal 0 V to 10 V
- Output impedance: Approx. 10 Ω
- Number of alarm points: 4 points + 4 points (extended allocation setting)
Setter specification
- Output signal: Analog output 4 mA to 20 mA DC, 0 V to 1 V DC, 0 V to 10 V DC
- Digital output: RS-422A, RS-485
- Output update cycle: 0.1 second
- Accuracy rating: ±0.1% of output span
- Resolution: Approx. 1/50000
- Output impedance: Approx. 10 Ω
- Load current: Current output 400 Ω or less,Voltage output 50 kΩ or more